Chapter 4 • Hydran 201Ti's Displays and Menus
Table 4-6 - Messages That Can Be Displayed Following a Sensor Test
Message
Good
Replace SensSoon
Replace SensNOW
CableOpen
CableShort
Sensor Not Inst!
4.5.4.3
Battery
This function is used to read the battery voltage and set the battery's alarm parameters:
• Battery: Voltage reading at the battery's terminals.
• Batt.Alr LL: Set point of battery Low-Low alarm.
• Batt.Alr L: Set point of battery Low alarm.
• BattAlr Delay: Alarm delay for both set points.
A fail alarm is triggered if the voltage of the battery gets below the Low or Low-Low alarm
set point for a period of time longer than the delay.
Note: The BattAlr Delay parameter is reset each time the Setup Lost alarm condition is
detected. This parameter must be set to its former operation value after the alarm condition
has disappeared.
For explanations pertaining to the H201Ti's battery, see Section 2.7 on page 2-15.
4.5.4.4
ServiceData
This function is used to read the value of six internal parameters used by the General
Electric Canada personnel during Hydran 201Ti maintenance or troubleshooting
procedures:
• ServiceL
• ServiceI
4-20
Signification
Hydran 201 sensor operating properly
Decreased sensor sensibility, replace rapidly
Damaged sensor, replace immediately
Cable disconnected, broken or misconnected
Cable misconnected or short-circuited
Unable to perform the test
Rev. 6, March 2011