Test alarm devices

The programmable outputs of type "Alarm device" can be collectively
activated via menu H8/S5, which make it possible to test the alarm
devices. (The test cannot be started if fire alarm already is activated in
the system.). One or all control units can be selected. When the test
starts the alarm devices will be "on" for 1 second (±1s)
seconds (±1s), "on" for 1 second and so on.
NOTE! Also disabled (and silenced) alarm devices will be tested.
The test is stopped via menu H8/S5, if a fire alarm is activated in the
system or after one hour.

Test of routing equipment

Via menu H1 it's possible to test the "Fault condition" and "Fire
alarm" outputs for routing equipment (Fault tx, Fire brigade tx and
corresponding programmable outputs). Open door etc. will not affect
the test.
In menu H1, select "Yes" and press " " to start the test. A 060
seconds count-down starts.
100
activated
, indicated by LED "Fault tx activated" on the c.i.e. front.
After 30 seconds will also the "Fire alarm" output(s) be activated,
indicated by LED "Fire brigade tx" on the c.i.e. front. After additional
30 seconds the test will be ended and the outputs and LEDs will go
back to "normal" status.

Calibration of supervised outputs

The supervised (monitored) outputs have to be calibrated after the
101
installation.
This is done via a menu (H5/A1) in the c.i.e.
Calibration range is 4K7 – 50K or 470 nF – 5 x 470 nF. If the
calibrated value is outside the range respectively or if the actual value
differs from the calibrated value ± a small tolerance, a fault will be
generated.

Service signal

All smoke detectors get contaminated no matter what environment
they are mounted in. In some environments it goes faster than in
others – depending on type of activity etc.
98
Some COM loop unit outputs might be "on" a little longer.
99
The output activation will be continuously (steady). For the alarm devices
3377 and 3379, the tone with the highest priority level (and type "alarm
device") will be automatically selected.
100
NOTE! Fault condition outputs are normally activated in "normal" state,
i.e. they will in case of fault be de-activated.
101
C.i.e. outputs S0-S3: E-o-l resistor 33K. 1 – 5 resistors (33K) can be
used. 3364 outputs VO0-VO1: E-o-l capacitor 470 nF. 1 – 5 capacitors
(470 nF) can be used.
105
99
The "Fault condition" output will be