Mitsubishi Electric EHGT17D-YM9ED Service Manual page 32

Table of Contents

Advertisement

Request
code
129
Condensing temperature (T63HS) at the time of error
130
Thermostat ON time until operation stops due to error
154
Water circulation pump 1 - Accumulated operating time (after reset)
156
Water circulation pump 2 - Accumulated operating time (after reset)
157
Water circulation pump 3 - Accumulated operating time (after reset)
158
Water circulation pump 4 - Accumulated operating time (after reset)
162
FTC - DIP SW1 setting information
163
FTC - DIP SW2 setting information
164
FTC - DIP SW3 setting information
165
FTC - DIP SW4 setting information
166
FTC - DIP SW5 setting information
175
FTC - Output signal information
176
FTC - Input signal information
177
Mixing valve opening step
190
FTC - Software version 1st 4 digits
191
FTC - Software version last 4 digits
200
Initialisation of Function Setting
340
Water circulation pump 1 - Accumulated operating time reset
342
Water circulation pump 2 - Accumulated operating time reset
343
Water circulation pump 3 - Accumulated operating time reset
344
Water circulation pump 4 - Accumulated operating time reset
504
FTC - Zone1 room temp. (TH1A)
505
FTC - Ref. liquid temp. (TH2)
506
FTC - Return water temp. (THW2)
507
FTC - Zone2 room temp. (TH1B)
508
FTC - DHW tank lower water temp. (THW5B)
509
FTC - Zone1 flow water temp. (THW6)
510
FTC - Outside air temp. (TH7)
511
FTC - Flow water temp. (THW1)
512
FTC - Zone1 return water temp. (THW7)
513
FTC - Zone2 flow water temp. (THW8)
514
FTC - Zone2 return water temp. (THW9)
515
FTC - Boiler flow water temp. (THWB1)
534
FTC - DHW tank upper temp. (THW5A)
535
FTC - Mixing tank water temp. (THW10)
540
Flow rate of the primary circuit
550
FTC - Error postponement history 1 (latest)
551
FTC - Operation control at time of error
FTC - Operation mode at time of error
552
553
FTC - Output signal information at time of error
554
FTC - Input signal information at time of error
555
FTC - Zone1 room temp. (TH1A) at time of error
556
FTC - Zone2 room temp. (TH1B) at time of error
557
FTC - Ref. liquid temp. (TH2) at time of error
558
FTC - Flow water temp. (THW1) at time of error
559
FTC - Return water temp. (THW2) at time of error
560
FTC - DHW tank water temp. (THW5B) at time of error
561
FTC - Zone1 flow water temp. (THW6) at time of error
562
FTC - Zone1 return water temp. (THW7) at time of error
563
FTC - Zone2 flow water temp. (THW8) at time of error
564
FTC - Zone2 return water temp. (THW9) at time of error
565
FTC - Boiler flow water temp. (THWB1) at time of error
FTC - Failure (P1/P2/L5/L8/Ld) thermistor
567
568
Mixing valve opening step at time of error
Operated Flow switch at time of failure (L9)
569
571
Flow rate at time of error
Note
As only 4 digits can be displayed at one time the software version number is displayed in two halves.
Enter code 190 to see the first 4 digits and code 191 to see the last 4 digits.
For example software version No. 5.01 A000, when code 190 is entered 0501 is displayed, when code 191 is entered A000 is displayed.
Request code 200 resets all Function Setting to the factory default settings.
OCH722A
Request content
Description
(Display range)
−39 to +88
0 to 9999
0 to 9999
0 to 9999
0 to 9999
0 to 9999
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
0 to 10
Refer to Note below.
Refer to Note below.
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−40 to +140
−39 to +88
−40 to +140
0 to 100
Displays postponement code.
("– –" is displays if no postponement code is
present.)
0 Standard, 1 Heater, 2 Boiler
0: OFF, 1: DHW, 2: Heating, 3: Cooling,
4: Legionella prevention, 5: Freeze protection,
6: Operation stop, 7: Defrost
Refer to detail contents described hereinafter.
Refer to detail contents described hereinafter.
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−39 to +88
−40 to +140
0: Failure thermistor is none, 1: TH1A, 2: TH2,
3: THW1, 4: THW2, 5: THWB1, 6: THW5B,
8: TH1B, A: THW6, B: THW7, C: THW8, D:
THW9
0 to 10
0: No operated flow switch, 1: Flow switch 1,
2: Flow switch 2,
3: Flow switch 3
0 to 100
32
Unit
Remarks
°C
Minutes
10 hours
10 hours
10 hours
10 hours
Step
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
L/min
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
°C
Step
L/min