300 or more
600 or more
❋ When 3 sides of the outdoor unit are blocked by the wall
600 or more
❋ When front and rear side of the outdoor unit is towards the wall
1500 or more 600 or more 3000 or more
❋ When front and rear side of the outdoor unit is towards the wall
• The units must be installed according to distances declared, in order to permit accessibility from each side, either to
guarantee correct operation of maintenance or repairing products.
CAUTION
The unit' s parts must be reachable and removable completely under safety condition (for people or things).
• Should adopt bar type louver. Don't use a type of rain resistance louver.
[Bar type louver]
WARNING
• Louver specifications.
- Angle criteria : less than 20˚
- Opening ratio criteria : greater than 80%
600 or more
600 or more
600 or more
3000 or more
[Rain resistance louver]
300 or more
300 or more
❋ The upper part of the outdoor unit and
the air outlet is towards the wall
300 or more