ABB Relion 670 Series Applications Manual page 440

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 16
Logic
16.8.2
Application
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary (logical)
signals into an integer. It can be used – for example, to connect logical output signals from a
function (like distance protection) to integer inputs from another function (like line differential
protection). B16I does not have a logical node mapping.
The Boolean 16 to integer conversion function (B16I) will transfer a combination of up to 16 binary
inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the table below
from 0 to 32768. This follows the general formula: INx = 2
on the activated INx will be available on the output OUT as a sum of the values of all the inputs INx
that are activated. OUT is an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it
corresponds to that integer 65535 is available on the output OUT. B16I function is designed for
receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze the output at
the last value.
Values of each of the different OUTx from function block B16I for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block B16I.
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.
434
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© Copyright 2017 ABB. All rights reserved
x-1
where 1≤x≤16. The sum of all the values
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Input 6
32
Input 7
64
Input 8
128
Input 9
256
Input 10
512
Input 11
1024
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
1MRK 511 401-UUS F
SEMOD175832-4 v4
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Bay control REC670
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents