27. Valve leak test (valve
proving)
Menu level 1
Menu level 2
Params & Display
BurnerControl
Example of fuel train
Legend
Building Technologies

9.4 Extra functions of the LMV5

Menu level 3
ValveProving
The gas volume contained in the piping between the valves (including the valve
volume) must be calculated in accordance with the type of gas train.
G
Program
SV
Figure 83: Extra functions of the LMV5
Determination of the test time with predefined leakage rate to be detected during
valve proving:
(P G - P w )
V
t Test =

P atm
Q Leck
Determination of the detected leakage rate during valve proving:
(P G - P w )
Q Leck =

P atm
t Test
Q Leck
in l/h
Leakage rate in liters per hour
P G
in mbar
Overpressure between the valves at the beginning of the test phase
P W
in mbar
Overpressure set on the pressure switch (normally 50% of the
gas inlet pressure)
P atm
in mbar
Absolute air pressure (1,013 mbar normal pressure)
V
in l
Volume between the valves (test volume)
including valve volume and pilot path (Gp1) if present
t Test
in s
Test time
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
ValveProvingType
Config_PS-VP/CPI
VP_EvacTme
VP_TmeAtmPress
VP_FillTme
VP_Tme_GasPress
Direct ignition
V1
PS
PS
min
VP
3600
V
3600
Menu level 5
Menu level 6
V2
PS
ACT
max
7550s01E/0202
181/327
CC1P7550en
22.05.2018