Download Print this page

Siemens MKB-1 Operating Instructions Manual page 15

Mxl multi-line keyboard/display panel
Hide thumbs Also See for MKB-1:

Advertisement

Viewing the List of Troubles
How to Individually Acknowledge a Trouble (NFPA 72 Proprietary, UL 1076)
How to Block Acknowledge a Trouble (NFPA 72 Local, 72 Municipal Tie, 72 Remote Station)
Siemens Building Technologies
Fire Safety
If your System includes a printer, it prints a message from two to four lines long
similar to the following:
TROUBLE IN
1-1
#2 [custom message], [trouble type], [device type]
In the above printed message, TROUBLE indicates that the type of occurrence is a
trouble; 1-1 is the device address; and #2 is the number of troubles in the list of
troubles; [custom message] is a custom message entered using the CSG-M
Custom Software Generator (See the CSG-M Programming Manual, P/N 315-090381);
[trouble type] is the type of trouble which reported; [device type] is the type of
device in trouble.
To see the trouble list when there are more than eight troubles, press the DOWN key
on the MKB. (If your system is set for Canada, the system displays the oldest event
first.)
The first, unACKnowledged, trouble will be placed in line nine. Press TRBL
ACK. The System acknowledges the trouble displayed and then places the
second, unACKowledged trouble in line nine (the fixed line). If your System
has the printer option, it prints an acknowledgment message similar to the
following:
ACK Trouble
#2 [custom message],[trouble type], [device type]
Note that the acknowledgment message includes the term ACK to indicate
this trouble was acknowledged.
Continue acknowledging troubles as explained above until the System
displays the following message:
ALL TROUBLES ACKNOWLEDGED
The TROUBLE LED glows steadily to indicate that all troubles are acknowl-
edged. If there are no security conditions still in the System, the internal
audible goes silent; if any of those conditions still exist, the internal audible
pulses.
If your System includes a printer, it prints the following message:
ACK Trouble
All Troubles Are Now Acknowledged.
Note the specific location of the trouble(s) by using the procedures de-
scribed above.
Unlock and open the door.
Press TRBL ACK to acknowledge all troubles. The System displays the
following message:
ALL TROUBLES ACKNOWLEDGED
11:59:59 Dec 31, 20
1-5
12:01:28 Dec 31,20
12:05:44 Dec 31, 20
15
P/N 315-048692-2

Advertisement

loading

This manual is also suitable for:

Mkb-2Mkb-3Mkb-4Mxl