Designation
Minimum measurable mains voltage between N and L
Measurable line frequency final value
Measurable line frequency initial value
Power consumption of the power supply
Measuring category for voltage measurement
Minimum measurable current at AC
Maximum measurable current at AC
Radio regulations EU
Radio transmission frequency
Radio transmission power
10.5

3NA COM fuse

Designation
Order number
Product name
Tripping characteristic class
Versions
Size
Operational current for AC rated value
Available measurement data
Switching capacity current in accordance with IEC 60947-2
Supply voltage for AC rated value
Factor tripping rule for test current
Measuring accuracy of current measurement at reference
temperature 25°C
Measuring accuracy of current measurement in the range -
10°C ... +70°C
Temperature measuring range
Measuring accuracy of temperature measurement
active power input per phase during current measurement
Power loss maximum (dependent on rated current)
Minimum ambient temperature during storage
Maximum ambient temperature during storage
Maximum ambient temperature during operation
Minimum ambient temperature during operation
Maximum relative humidity / 25°C without condensation
during operating
IP degree of protection
Pollution degree
Reference condition for measuring accuracy
Measuring method
Circuit protection devices with communication and metering function
System Manual, 06/2021, L1V30827018B-01
Value
50 V
60 Hz
45 Hz
0.4 VA
CAT III acc. to IEC 61010-2-030
0.02x I
0.04 A
n
2x I
n
2014/53/EU
2400 - 2483.5 MHz
10 dBm
Value
3NA32xx-4KK0y (xx = 24, 30, 32, 36, 40, 42, 44, 52; y = 1,
2, 3, 4)
3NA COM LV HRC fuse link
gG and gFF
With and without electronic module
NH2
80 A, 100 A, 125 A, 160 A, 200 A, 224 A, 250 A, 315 A
Current, temperature, operating hours, warnings
100 kA
400 V
1.45
1% (8 A ... 440 A), 2% (2.5 A ... 8 A)
2.2% (8 A ... 440 A), 3.2% (2.5 A ... 8 A)
+20°C ... +120°C
+/- 2.5°C
50 mW
9 W, 6.6 W, 10 W, 7.5 W, 13.6 W, 10 W, 16.5 W, 12.4 W,
22.3 W, 12.8 W, 13.5 W, 24 W, 17.5 W
-10°C
70°C
55°C
-10°C
95%
IP20
2
IEC 61557-12
TRMS
Technical specifications
10.5 3NA COM fuse