17.1 Table of Specificationa
17.1.1 General Specifications
Item
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Ambient storage humidity
Breakdown voltage
Insulation resistance
Vibration resistance
Shock resistance
Noise immunity
Operating environment
Internal current consumption
Weight
17-2
0 to +55
C
-20 to +70
C
30 to 85 % RH (at25
30 to 85 % RH (at25
1500 V AC, 1 minute
Between the various pins of the external connector and the ground
(However, excluding F.E. terminal)
100MΩ or more (measured with 500 V DC testing)
Between the various pins of the external connector and the ground
(However, excluding F.E. terminal)
10 to 55 Hz, 1 cycle/min.
Double amplitude of 0.75 mm, 10 min. each in the X, Y, Z directions
2
Shock of 98 m/s
, 4 times in the X, Y, Z directions
1500 V[P-P] with pulse widths 50ns and 1µs
(based on in-house measurements)
Free of corrosive gases and excessive dust
300 mA or less
Approx. 150 g
Description
C non-condensing)
C non-condensing)