Huawei UPS5000-H User Manual page 85

400 kva-800 kva. 100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-800 kVA)
User Manual (100 kVA Power Modules)
Item
Recommended
cross-sectional
area
Equipotentia
Recommended
l ground
cross-sectional
point
area (mm
Table 6-9 Recommended power cable cross-sectional areas (600–800 kVA)
Item
Mains input
Mains input current
(A)
Recommend
ed cross-
sectional
area (mm
Bypass input
Bypass input current
(A)
Recommend
ed cross-
sectional
area (mm
Output
Output current (A)
Recommend
ed cross-
sectional
area (mm
Battery input
Nominal battery
(lead-acid
discharge current (A)
battery)
Maximum battery
discharge current (A)
Issue 03 (2021-08-03)
200 kVA
For details, see the IEC-60364-5-52 specifications and
SmartLi User Manual .
16
2
)
600 kVA
882
L1
3 x 240
L2
3 x 240
2
)
L3
3 x 240
N
3 x 240
PE
240
722
L1
3 x 185
L2
3 x 185
2
)
L3
3 x 185
N
3 x 185
PE
240
722
U
3 x 185
V
3 x 185
2
)
W
3 x 185
N
3 x 185
PE
240
1330
1593
Copyright © Huawei Technologies Co., Ltd.
300 kVA
400 kVA
700 kVA
1030
4 x 185
4 x 185
4 x 185
4 x 185
240
842
3 x 240
3 x 240
3 x 240
3 x 240
240
842
3 x 240
3 x 240
3 x 240
3 x 240
240
1551
1858
6 Installation
500 kVA
800 kVA
1177
4 x 240
4 x 240
4 x 240
4 x 240
240
962
4 x 185
4 x 185
4 x 185
4 x 185
240
962
4 x 185
4 x 185
4 x 185
4 x 185
240
1773
2123
77

Advertisement

Table of Contents
loading

Table of Contents