Main Board Option Settings - GE Bently Nevada 3300/25 Operation Manual

Dual accelerometer input monitor
Table of Contents

Advertisement

18.3 Main Board Option Settings

Use these and the tables on the following pages to configure main board options:
OPTION
First Out
OK Mode
Timed OK/Channel
Defeat
Alert Mode
Danger Mode
Danger Bypass
Danger Relay Voting
Alarm Delays
NOTES:
*
Denotes standard configuration.
**
Nonlatching OK mode MUST be selected if Timed OK/Channel Defeat is enabled.
The table is setup with this dependency in mind.
OPTION
Trip Multiply +
*** W21 is used only with Transducer Input/Channel Units options 01, 02 or 03.
+
Trip multiply options require hardware component changes on the main board. Do
not change the TM option unless corresponding hardware changes are made also.
Consult your local sales representative for information.
++
Do not use AND voting with Quad Relays.
Section 18 - Appendix A–Main Board Options
SETTING
Enabled*
Disabled
Latching
Nonlatching*
Enabled*
Disabled
Latching*
Nonlatching
Latching*
Nonlatching
Enabled
Disabled*
OR voting for relay drive*
AND voting for relay
0.1 Second
1 Second
3 Seconds*
6 Seconds
SETTING
INSTALL
None
W19A,W19B
2X
W15A,W21*
3X
W16A,W21*
INSTALL
REMOVE
W16C
None
None
W16C
W20, W23**
None
None
W23
None
W20, W23**
W20
None
W15D
None
None
W15D
W16B
None
None
W16B
W24
None
None
W24
None
W16D
W16D ++
None
None
W15B, W15C
W15C
W15B
W15B
W15C
W15B, W15C
None
REMOVE
W15A,W16A,W21
W16A,W19A,W19B
W15A,W19A,W19B
49