Panasonic Electric Works Fire & Security Technology Europe AB
MEW00748
27.9
Action
"Access"
Scroll to menu A8
"A"
"A"
or
"1", "A"
"A"
"Return"
Rev: 1
Select unit on COM-loop to use for trigging
(H5/A8)
This function is used by service engineer and by R&D for
troubleshooting.
On the pin respectively you will get a pulse to trig an oscilloscope etc.
COM loop
Main board 1556, JP2, "upper" pin: Each unit not giving a correct
answer.
Main board 1556, JP2, "lower" pin: A specific unit is being polled.
BS4 loop
Autronica interface board 1584 (in the c.i.e.), BY3, "left" pin: A
specific unit is being polled.
Autronica interface board 1584, BY3, "right" pin: 0 V.
(BS4 board = Autronica interface board 1584)
Text in display
Select unit on COM-/BS4-loop to use for
trigging
Select type of loop: 0 (0=COM, 1=BS4)
CU: 00 Loop: 0 Address: 000
CU 00, BS4-Board 0, Loop: 0, Address: 00
Select type of loop: 0 (0=COM, 1=BS4)
Select unit on COM-/BS4-loop to use for
trigging
Operating Instructions Fire alarm system EBL512 V2.3.x
ACCEPT? A8
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT?
ACCEPT? A8
112
Comments
According to chapter
"Access code for service
(H5)", see page 104.
Select type of loop. Press
"A" to accept.
Write control unit number,
(board number; 0-3), loop
number and address. Press
"A" to accept.
Select type of loop. Press
"A" to accept or press
"Return" to menu A8..
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.