Huawei FusionDC1000A Maintenance Manual page 39

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:
Table of Contents

Advertisement

FusionDC1000A Prefabricated All-in-One Data
Center
Maintenance Guide (IT Scenario)
Check Item
Content
RUN indicator
RF_Z indicator
PAD
Exterior
Exit button
Function
Issue 01 (2021-04-20)
Check Standard
Off: The power supply is
abnormal.
Blinking at long intervals: The
device successfully registers
with the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at short intervals: The
communication is disconnected
or the device fails to register
with the ECC800-Pro (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking: The indicator blinks at
super short intervals for 0.5s
(blinking at 10 Hz, on for 0.05s
and then off for 0.05s) and
then turns off for 0.5s. The
cycle lasts for 10s.
On: No network parameters
exist. A network is waiting to
be created.
Blinking slowly: A network is
set up, and node access is not
allowed (the indicator blinks at
0.5 Hz, on for 1s and then off
for 1s).
Blinking at super short
intervals: A network is set up,
and node access is allowed (the
indicator blinks at 10 Hz, on for
0.05s and then off for 0.05s).
Blinking at super short intervals
intermittently: The device is
searching for a network (the
indicator blinks at 2 Hz, on for
0.5s and then off for 0.5s).
The exterior is intact and the
touchscreen is working
properly.
The function is normal.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Check the power supply.
See the ECC800-Pro
documents.
See the ECC800-Pro
documents.
Replace the PAD.
Replace the exit button.