Acknowledging alarms
Received alarms from the selected channel are acknowledged using the <ACK> key, i.e. the
alarm is reset.
Condition: P.14/AcK = "¬St.Ac" or "St.Ac"
The following can appear in the digital display as soon as you press the <ACK> key:
Pre-alarm or main alarm received:
No alarm received:
Note
The alarms are reset after 5 seconds. If you release the <ACK> key within these 5 seconds,
the alarms are not reset.
See also
Parameter table (Page 6-7)
6.3.3

Universal inputs

Overview
There are four universal inputs. They can be used for monitoring the membranes and the oil
bath on the pump, for example.
Display of channel numbers for universal inputs in digital display:
• 5/In 1
• 6/In 2
• 7/In 3
• 8/In 4
The universal inputs are configured using parameters P.26 to P.29. The display is different
depending on the configured function of the relevant input.
Function as analog input
With the setting of the associated parameters to "0-20", "4-20", "20-0" or "20-4", a
normalization of the analog current (in mA) from 0 to 100% takes place. E.g.:
20-4 -> 20 mA = 0% / 4 mA = 100%
This percentage value is displayed as the measured value and monitored for a configurable
limit value (parameters P.30 to P.33).
SITRANS DA400 with protection against explosion
Operating Instructions, 02/2006, A5E00684661-01
rES (flashing)
noAL
Operation
6.3 Measuring menu
6-5