Forced Cooling Operation; Setting Procedure - LG Multi F A2UW14GFA0 Engineering Product Data Book

Heat pump 50hz/r410a
Table of Contents

Advertisement

3. Installation of outdoor unit
14/16/18/21(1Ø) kBtu/h
24/27/30(1Ø) kBtu/h
SW01N
65 _ Heat pump
50Hz/R410A
DIP-SW
40/48/56(1Ø) kBtu/h
42/48/56(3Ø) kBtu/h

3.10.2 Forced Cooling Operation

Adding the refrigerant in winter.

Setting Procedure

1. Set the Dip Switch as follow after shutting the
power source down.
2. Reset the power.
3. Check that the Red LED of PCB is on during work.
(The indoor unit is operated by force.)
4. Add the specific amount of refrigerant.
CAUTION
• When the green LED of PCB is on, compressor is
going to be off because of low pressure.
• You should return the Dip Switch to operate normal-
ly after finishing the operation.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents