3.4.9.2
Derating factors as a function of the ambient temperature
The units can supply 100 % output current at an ambient air temperature of between 0 °C
and 45 °C. The maximum output current decreases linearly to 90 % at ambient air
temperatures of between 45 °C and 50 °C.
Figure 3-31
Liquid-cooled chassis power units
Manual, (GH7), 11/2016, 6SL3097-4AM00-0BP7
Maximum current as a function of ambient temperature
Line-side power components
3.4 Active Interface Modules, liquid-cooled
103