If you are familiar with the structure of the settings in DIGSI 5 and on-site operation, you can navigate through
the same structure (for example function groups, function blocks, and the diagram on the on-site operation
panel) using the browser-based user interface.
The PC that you wish to use to operate the SIPROTEC 5 device must be connected to the device via a network
cable. The PC and the SIPROTEC 5 device must be switched on.
Before you operate the device using a Web browser, you first have to check the security settings. With the
security settings, you restrict the access rights for Web access (Port J and Ethernet communication module).
You can define the security settings in DIGSI in the project tree under Security → Network access security.
You can assign the following access rights:
•
No access:
This interface does not allow access to the device.
•
Read-only access:
This interface only allows read access to the device.
•
Read/write access (default setting):
This interface allows read and write access to the device.
To operate the device via the browser-based user interface, proceed as follows:
•
Connect the SIPROTEC 5 device (for example Port J) to your PC using a network cable.
NOTE
i
i
If the device has an Ethernet communication module, you can also use the ports E, F, N, or P, or you can
access the device via the USB interface.
NOTE
i
i
To access the device via the USB interface, use the following IP address: 192.168.2.1.
In order to access the device via the integrated Port J, define the following setting of the access under
Network access security in DIGSI:
[sc_webaccess, 2, en_US]
Figure 7-1
NOTE
i
i
Note the IP address and the port number of the interface used for communication between the PC and the
browser-based user interface. Make sure that the 12-digit IP address for the Web browser has been
correctly set using the format ***.***.***.*** via DIGSI.
•
Launch the Web browser on your PC.
•
Enter the IP address of the device in the address line of the Web browser, followed by the port number
4443, for example https://172.16.60.60:4443, and confirm the entry using the ENTER key.
NOTE
i
i
You may operate the SIPROTEC 5 device using DIGSI 5 and using the browser-based user interface in
parallel.