7.2

Operation

If you are familiar with the structure of the settings in DIGSI 5 and on-site operation, you can navigate through
the same structure (for example function groups, function blocks, and the diagram on the on-site operation
panel) using the browser-based user interface.
The PC that you wish to use to operate the SIPROTEC 5 device must be connected to the device via a network
cable. The PC and the SIPROTEC 5 device must be switched on.
Before you operate the device using a Web browser, you first have to check the security settings. With the
security settings, you restrict the access rights for Web access (Port J and Ethernet communication module).
You can define the security settings in DIGSI in the project tree under Security → Network access security.
You can assign the following access rights:
No access:
This interface does not allow access to the device.
Read-only access:
This interface only allows read access to the device.
Read/write access (default setting):
This interface allows read and write access to the device.
To operate the device via the browser-based user interface, proceed as follows:
Connect the SIPROTEC 5 device (for example Port J) to your PC using a network cable.
NOTE
i
i
If the device has an Ethernet communication module, you can also use the ports E, F, N, or P, or you can
access the device via the USB interface.
NOTE
i
i
To access the device via the USB interface, use the following IP address: 192.168.2.1.
In order to access the device via the integrated Port J, define the following setting of the access under
Network access security in DIGSI:
[sc_webaccess, 2, en_US]
Figure 7-1
NOTE
i
i
Note the IP address and the port number of the interface used for communication between the PC and the
browser-based user interface. Make sure that the 12-digit IP address for the Web browser has been
correctly set using the format ***.***.***.*** via DIGSI.
Launch the Web browser on your PC.
Enter the IP address of the device in the address line of the Web browser, followed by the port number
4443, for example https://172.16.60.60:4443, and confirm the entry using the ENTER key.
NOTE
i
i
You may operate the SIPROTEC 5 device using DIGSI 5 and using the browser-based user interface in
parallel.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Security Setting in DIGSI
Operation Using a Browser-Based User Interface
7.2 Operation
109