7. Press Enter to highlight and then the Up or Down arrow buttons to fill the Restore checkbox. This action
restores the backup file. If there is an error during the process, the specific error is displayed on this
screen.
8. Cycle power to the controller

AC Smart Setup

1. Confirm control wiring between rooftop unit Carel controller and AC Smart 5 Channel 1 (wiring is 18 AWG, 2
conductor, twisted, stranded, shielded, and must comply with all applicable local and national codes.)
2. Note that AC Smart 5 or later version must be used with Carel controller. AC Smart 4 is not compatible with
Carel controller
3. Device ID on Carel controller, under "Network Settings" should be set as follows
a. AR-DE models: Carel Device ID = 17 (decimal) and AC Smart Address = 11 (hex)
b. AR-DR models: Carel Device ID = 18 (decimal) and AC Smart Address = 12 (hex)