4.3 Commissioning

Context
Procedure
Step 1 Set parameters for general input units on the ECC800-Pro WebUI.
1.
Issue 05 (2020-10-15)
The ECC800-Pro operation description is applicable to the software version
V100R003C00.
In the NMW scenario, general input units and power distribution units
communicate with the ECC800-Pro using the Modbus-MAC protocol.
After the general input units and power distribution units properly connect to
the ECC800-Pro, the ECC800-Pro automatically identifies the units.
Then, you need to set parameters for the general input units and power
distribution units; otherwise, a false alarm may be generated.
Set parameters for general input unit 1.
Table 4-1 Power distribution settings for a general input unit
Path
Monitoring >
Power
Distribution >
General Input
Unit > Running
Parameters >
Power
Distribution
Settings
Copyright © Huawei Technologies Co., Ltd.
Parameter
Default
Name
Value
Rated system
50
frequency
Rated system
380
voltage
Rated system
250
current (This
parameter is
not displayed
for some
general input
units.)
System CT
250
ratio (This
parameter is
not displayed
for some
general input
units.)
4 Power-On Commissioning
Setting
Set based on actual
conditions.
Set based on actual
conditions.
Set based on actual
conditions.
Set this parameter to a
value consistent with
the information on the
nameplate of the
general input unit. For
example, if the model is
NMW-0250 AC, set
Rated system current
to 250 A.
Set based on actual
conditions.
For example, if Rated
system current is 250
A, set System CT ratio
to 250.
45