FC700A
Fire detection system
Maintenance instructions
Fire & Security Products
Siemens Building Technologies

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FC700A

  • Page 1 FC700A Fire detection system Maintenance instructions Fire & Security Products Siemens Building Technologies...
  • Page 2 Sous réserve de modifications techniques et de la disponibilité. © 2004 Copyright by Siemens Building Technologies AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist.
  • Page 3: Table Of Contents

    Power supply check ................13 Control unit check.................14 Control terminal check .................15 System performance check ..............16 Schedule for the performance check ............16 Intervals for the detector overhaul at factory ..........17 Concluding work ...................18 Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 5: About This Document

    Scope This instruction covers the maintenance work on the control unit type FC700A with standard equipment. They are a basic part of the general maintenance guidelines for fire detection systems and must be applied for all periodic maintenance work.
  • Page 6 The document number consists of: Language, number, index – Version date – bottom right – Manual Register – Modification index Version Date Brief description 007833_a_en_-- 03. 2004 First edition Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 7: Safety Regulations

    The symbols listed below indicate the nature and origin of the danger. Signal word General danger Signal word Electrical voltage Example for a danger warning DANGER Disconnect the module from power supply. External voltage Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 8: Classification And Meaning Of Additional Symbols

    This espe- cially applies when switching-off system components. In the case of extinguishing systems, always use the ”General installation in- structions” as a guideline. This guideline is available on request. Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 9 Batteries require environmentally safe disposal. They must be handed in at the local collecting points. Please take into account that the extinguishing agent cylinders are pressurized and must be exchanged in compliance with the local safety regulations. Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 10: Test And Measuring Equipment

    Test lamp LE3, StabexHF for explosion hazard areas – Line tester Depending on detector type For collective detector lines Alarm test probe (5.6V Zener diode with 220Ω resistor) – For addressable detector lines Line test unit DZ1131 – Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 11: Preparatory Work

    Time schedule must be determined with the system operator for the following test sequences: Alarm tests (incl. remote transmission) – Performance check of fire control installations – Any follow-up training – Any clarification – Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 12: System Data

    Replace all detectors in "Drift" conditions. Change of use Inspect all reported changes to the building, especially rooms with new utilization. Make all necessary modifications to the FC700A system with regards to this change. Planned modifications Check whether all modifications have been carried-out, e.g. changes to diagrams,...
  • Page 13: Power Supply Check

    Check the lithium auxiliary batteries by disconnecting the power supply for approx. 15 minutes. After switching-on again, check the date, time and fault message. If there is any loss of date, replace the corresponding unit. Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 14: Control Unit Check

    Control unit check Control unit check Hardware Assess the condition of the housing, visual check on hardware modules and batter- ies. Check mounting screws, terminals and plug-in connections. Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 15: Control Terminal Check

    5. Activate 1 ALARM, acknowledge and reset. 6. Activate 1 FAULT, acknowledge and reset. 7. Log-out. Cleaning Clean display window and front panel with mild soap. Do not use abrasive sol- vents. Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 16: System Performance Check

    Check for each line whether a short circuit / open line acti- vates a FAULT signal. Check the loop line function. During the short circuit also check the isolator function. Overhaul at the factory of all automatic fire detectors. See chapter 9.2 Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 17: Intervals For The Detector Overhaul At Factory

    Production halls and assembly areas – Cable ducts, risers, elevated floors – Wood industry, textile industry – High risk, e.g.: Rooms and areas with high value concentration or sensitive work processes. – Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...
  • Page 18: Concluding Work

    Refurbish spare parts like fuses, detectors, etc. Deactivations, zone isolations Restore all systems or parts of systems to their active status. Confirmation Have the customer / system operator sign the service report? Siemens Building Technologies 007833_a_en_--.doc Fire & Security Products 03.2004...