The diagram below shows how an OPC UA client (A) calls the server method "Cool":
The CPU executes the instance "Cool1" of the server method "Cool" in the cyclic user
program
The CPU first uses the instruction "OPC_UA_ServerMethodPre" to query
OPC UA client has called the server method "Cool"
● If the server method has not been called, program execution returns directly to the cyclic
user program over
● If the server method has been called, this information is returned to the server method
"Cool" over
see"<Method Functionality>" in the graphic.
The server method then uses the instruction "OPC_UA_ServerMethodPost"
the firmware (B) that the instruction has been executed
The firmware returns this information over
Communication
Function Manual, 11/2019, A5E03735815-AH
.
and
. The actual functionality is now executed in the Cool server method,
9.3 Using the S7-1500 as an OPC UA server
.
. The CPU resumes the cyclic user program after "Cool1".
to the calling OPC UA client (A).