Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
3.2.9
CFSK (Message Type i)
CFSK Example
SIA Mode Description
<LF><CRC><I><sequence#><Receiver#><line#>[#aaaaaa|TTEE]<CR>
Table 55: CFSK (Message Type i) Byte Description
Title
LF
CRC
Message Type
sequence#
receiver#
line#
(Line/Group #)
account #
TT
EE
52
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
Description
Standard line feed character.
Cyclical redundancy check number.
i.
The message sequence number. The valid sequence number range is
0001 to 9999.
The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
The line number of the line in the receiver gateway that sent the message.
Valid digits are 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
The communicator's account number, up to six digits.
Event code.