VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Table of contents Change from one to two columns Transport and storage ..........37 Safety ................4 General information and instructions ........4 Inspection ................37 ...
Page 3
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Maintenance ............. 58 Safety instructions ..............58 Cleaning ................... 58 Sensor ..................58 Repair ................ 59 Safety instructions ..............59 Spare parts ................
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 1 Safety hange from one to two columns Warnings General information and instructions The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
Repairs, alterations, and enhancements, or the installation of replacement parts, are only permissible insofar as these are described in this manual. Approval by ABB Automation Products GmbH must be sought for any activities beyond this scope. Repairs performed by ABB-authorized specialist shops are...
Email: automation.service@de.abb.com leakage and / or theft of data or information. ABB Automation Products GmbH and its affiliates are not liable for damages and / or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and /...
Note Further information on the Ex-Approval of devices can be found in the type examination certificates or the relevant certificates at www.abb.com/flow Device overview The devices are designed for maximum versatility. This is achieved through a combination of several types of protection within each device.
Depending on the design, a specific marking in accordance with ATEX or IECEx applies. • ABB reserves the right to modify the Ex-marking. Refer to the name plate for the exact marking. Model FAM54xAx (analog indicator without alarm signaling unit)
Page 9
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Model FAM54xE/Fx (analog indicator with transmitter and with or without LCD indicator) Marking Type of protection Order code* Limit value table ATEX II 1/2 G Ex h ia IIC T4 ... T1 Ga/Gb Intrinsically Safe Table 1 on page 14 II 1/3 G Ex ec h ic T6 ...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Installation instructions The installation, commissioning, maintenance and repair of Protection against electrostatic discharges devices in areas with explosion hazard must only be carried out DANGER by appropriately trained personnel.
Devices with ½” NPT threads and ATEX and IECEx approvals can Note be ordered and operated without cable glands (with the Spare parts can be ordered from ABB Service. exception of ‘Ex d’). In this case, the operator is responsible for www.abb.com/contacts properly installing pipe fittings in accordance with national regulations (e.g.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Installation instructions Type of protection Ex d - flameproof (enclosure) The outside diameter of the unshielded connection cable must Model FAM540, order code A9 be in a range from 7.2 to 11.7 mm (0.3 to 0.5 in).
Page 13
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Earthing Figure 3: Terminals 31 / 32, power supply / load Power supply 1 Ground terminal Maximum permissible load in the power supply (z. B. indicator) 2 Potential equalization in accordance with EN 60079-0 The minimum voltage U = 0 V is based on a load of 0 Ω.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx Safety specifications ATEX / IECEx Special conditions for type of protection ‘Ex td’ (dust explosion protection) Model FAM54xB/C/D/E/Fx The following differing temperature data applies to usage in areas with combustible dust.
Page 15
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E A4, A9, B1 ATEX: 31 / 32 = 46 V 40 °C 440 °C II 1/3 G Ex ec h ic IIC T6 ... T1 Ga/Gc 40 °C 375 °C II 2 D Ex h tb IIIC T85°C ...
Page 16
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Safety specifications ATEX / IECEx Table 2: Analog indicator with alarm signaling unit Model FAM54xB/C/Dx Type of protection: intrinsic safety, dust explosion protection.
Page 17
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Table 3: Analoganzeiger mit Grenzwertgeber Model FAM54xB/C/Dx Type of protection: flameproof enclosure, dust explosion protection. Order Marking Terminals Electrical values Temp. class Insulation medium code −20 °C to (−50 °C to ) Maximum ATEX: 41 / 42...
Page 18
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Safety specifications ATEX / IECEx Table 4: Analoganzeiger mit Grenzsignalgeber Model FAM54xB/C/Dx Type of protection: non-sparking materials, dust explosion protection. Order Marking Terminals...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Table 5: Analoganzeiger ohne Grenzsignalgeber Model FAM54xAx Type of protection: constructional safety, dust explosion protection Order Marking Terminals Electrical values Temp. class Insulation medium code* −20 °C to (−50 °C to ) Maximum A4, A9, B1 ATEX: n.a.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Change from two to one column … 2 Use in potentially explosive atmospheres in accordance with ATEX and IECEx … Operating instructions Changing the type of protection Depending on the model, the device may be designed to be installed in one of the applications listed. If you plan to use a device that was installed in one type of protection rating in a different type of protection rating, some measures must be taken before connecting voltage to the device.
Note Further information on the Ex-Approval of devices can be found in the type examination certificates or the relevant certificates at www.abb.com/flow Device overview The devices are designed for maximum versatility. This is achieved through a combination of several types of protection within each device.
Depending on the design, a specific marking in accordance with FM applies. • ABB reserves the right to modify the Ex-marking. Refer to the name plate for the exact marking. Model FAM54xAx (analog indicator without alarm signaling unit and model FAM54xB/C/Dx (analog indicator with alarm signaling unit)
Only original spare parts must be used to seal the housing. regulations with regard to installation, function tests, repairs, and maintenance of electrical devices. (e. g. NEC, CEC). Note Spare parts can be ordered from ABB Service. Intrinsic Safety Control Drawing www.abb.com/contacts Note...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 3 Use in potentially explosive atmospheres in accordance with FM and cCSAus … Installation instructions Electrical connections 1 Strain relief 3 Gasket 2 Adapter M25 × 1.5 / ½“-NPT 4 Sleeve 5 Union nut 1 FM Approved IS Barrier...
Page 25
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Installation instructions Earthing The concept of intrinsic safety enables multiple intrinsic safety devices with FM or CSA approval to be interconnected, without entity parameters being examined specifically, subject to observation of the following conditions: •...
Page 26
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 3 Use in potentially explosive atmospheres in accordance with FM and cCSAus … Installation instructions Power supply Installation must comply with the requirements of the ® National Electric Code (ANSI / NFPA70).
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Safety specifications FM, cCSAus Table 1: Analog indicator with alarm signaling unit (temperature data for FM in °F, for cCSAus in °C) Order Marking Terminals Electrical Temp. class Insulation medium code*...
Page 28
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 3 Use in potentially explosive atmospheres in accordance with FM and cCSAus … Safety specifications FM, cCSAus Table 2: Analog indicator with alarm signaling unit (temperature data for FM in °F, for cCSAus in °C) Order Marking Terminals...
Page 29
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Table 3: Analog indicator with / without alarm signaling unit (temperature data for FM in °F, for cCSAus in °C) Order Marking Terminals Electrical values Temp. class Insulation medium code* −58 °F to...
Page 30
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 3 Use in potentially explosive atmospheres in accordance with FM and cCSAus … Safety specifications FM, cCSAus Table 4: Analog indicator with transmitter, with or without LCD indicator (temperature data for FM in °F, for cCSAus in °C) Order Marking Terminals...
Page 31
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Continuation of Table 4: Analog indicator with transmitter, with or without LCD indicator (temperature data for FM in °F, for cCSAus in °C) Order Marking Terminals Electrical values Temp.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 3 Use in potentially explosive atmospheres in accordance with FM and cCSAus Operating instructions Protection against electrostatic discharges Changing the type of protection The device can be operated with various types of protection: DANGER •...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 4 Design and function General FAM540 metal cone variable area flowmeters have a proven design and are equipped with an analog, mechanical indicator or an intelligent two-wire transmitter, i.e. the power supply and the flow signal utilize the same leads.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 4 Design and function Device overview Model FAM541 FAM544 Standard design Hygienic design Measured error in accordance with VDE / VDI 3513 1.6 % qg = 50 % 1.6 % qg = 50 % Reproducibility 0.25 % of measured value...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 5 Product identification Name plate A Standard 5 Order number B ATEX / IECEx 6 Model number C FM / cCSAus 7 Electric data (Ex) 1 TAG Number 8 IECEx Approval 2 Nominal diameter and IP rating 9 ATEX Approval...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 5 Product identification Factory tag Pressure equipment outside the scope of the Pressure The factory plate is on the flowmeter in addition to the name Equipment Directive plate.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 6 Transport and storage Inspection Storage Check the devices immediately after unpacking for possible Bear the following points in mind when storing devices: damage that may have occurred from improper transport. •...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 7 Installation Installation conditions • The installation recommendations of VDI / VDE Directive 3513 must be observed. • The flowmeter is installed vertically in the piping. The measuring media must flow from bottom to top. •...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Operating conditions Pressure loss A variable area flowmeter is specified for a defined set of The available operating pressure at the measuring point must be operating conditions of the measuring medium. For liquids and higher than the pressure loss listed for the flowmeter in the gases, these are pressure and temperature-related properties specifications.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 7 Installation … Operating conditions Solids content in the measuring medium Measuring range limits Variable area flowmeters have only limited suitability for measuring media containing solids. Depending on the concentration, particle size and type of solid, increased mechanical abrasion may occur, especially at the critical measuring edge of the float.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Installation of the flowmeter Note The device can be installed at any location in a pipeline under Torques for screws depend on temperature, pressure, screw and consideration of the installation conditions. gasket materials.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 7 Installation … Mounting Electrical connections DANGER Improper installation and commissioning of the device carries a risk of explosion. For use in potentially explosive atmospheres, observe the information in Use in potentially explosive atmospheres in accordance with ATEX and IECEx on page 7 and Use in potentially explosive atmospheres in accordance with FM...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Switching amplifier Analog indicator with transmitter Model FAM54xE/Fx Specifications Power supply 230 V AC, +10 % / −15 %, 45 to 60 Hz 115 V AC, +10 % / −15 %, 45 to 60 Hz 24 V DC, +10 % / −15 % Output One or two switching relays with potential-free...
Other tool or system integrations (e.g. Emerson AMS / Siemens PCS7) upon request. The necessary DTMs and other files can be downloaded from www.abb.com/flow. Programmable binary output Terminals 41 / 42 are used as a primary programmable binary output. The pulse output, general alarm, min./max. alarm and general alarm functions, as well as "no function"...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 8 Commissioning Switching on the power supply DANGER The following points must be checked before commissioning the Improper installation and commissioning of the device device: carries a risk of explosion. •...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 8 Commissioning Adjusting the alarm signalling unit Configuring the programmable output The switch output of the transmitter is configured by default as a NAMUR contact. The contact can also be configured as an optoelectronic coupler output.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 9 Operation Operating instructions DANGER When operating the device, please note the following: Danger of explosion if the device is operated with the • Aggressive or corrosive media can lead to damage of transmitter housing open! wetted parts.
The service menu is reserved exclusively for the after- Next Select the next position for entering numerical and sales-service of ABB Automation Products. It includes alphanumeric values the default settings of the device. It can only be accessed with the service code. Changes may cause the device to display incorrect information.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Parameterization of the device Parameter Overview Note This overview of parameters shows all the menus and parameters available on the device. Depending on the version and configuration of the device, not all of the menus and parameters may be visible in it. Menu / parameter Value range/Input type Remark...
Page 50
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 9 Operation … Parameterization of the device Menu / parameter Value range/Input type Remark ▲ Main Menu Pulse width Numerical Only active if a pulse output is selected. ►...
Page 51
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Menu / parameter Value range/Input type Remark ▲ Main Menu Operating density Numerical The density of the measuring medium has an ► Operating density 1.000000 influence on the moving force of the float. 1.000000 g/cm Min 0.000001 Precise input is essential for an exact...
Page 52
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 9 Operation … Parameterization of the device Menu / parameter Value range/Input type Remark ▲ Main Menu Current output Numerical The Edit can be used to set the behavior of the ►...
Page 53
Min 0 HART multidrop mode. Back Edit Back Edit ▼ ▲ Main Menu TAG number Enter a separate, 8-digit TAG number. ► TAG number ABB AM54 ABB AM54 Back Edit Back Edit ▼ ▲ Main Menu 20.04.2007 06:39:59 Back Edit...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 9 Operation Description of menus and parameters ‘Prog.Output’ Menu Standard densities for a few selected gases: In this menu, the programmable binary output (terminals 41 / 42) is parameterized . Standard density [kg/m3] The following settings are available: Acetylene...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E ‘Current output’ Menu ‘Function test’ Menu Configure the current output behavior for device alarms in the current output submenu. Submenu Adjustable Description The settings High and Low are available. values •...
• The ‘Specialist’ user level has an additional ‘Mains interrupt’ submenu, where the number of power outages is recorded. The power outage counter can only be reset by the ABB after- sales service. Change from two to one column...
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Error messages Message NE 107 classification Cause Remedy Error 1 Failure Hardware error on the front-end board. Please contact the service department. Front End Error 3 Out of Spec Overshoot of the device measuring range.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 11 Maintenance Safety instructions Corrective maintenance work may only be performed by trained DANGER personnel. Danger of explosion if the device is operated with the • Before removing the device, depressurize it along with any transmitter housing open! adjacent lines or vessels.
Danger of explosion if the device is operated with the make sure of obtaining traceable units that are in perfect transmitter housing open! working order, you can order them from ABB by specifying the Before opening the transmitter housing, bear in mind the original serial number.
All devices delivered to ABB must be free from any hazardous materials (acids, alkalis, solvents, etc.). Address for returns: Please contact Customer Center Service according to page 6 for nearest service location.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 13 Dismounting and disposal Dismounting Disposal WARNING Note Products that are marked with the adjacent symbol Risk of injury due to process conditions. may not be disposed of as unsorted municipal waste The process conditions, for example high pressures and (domestic waste).
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E 14 Specification Note The device data sheet is available in the ABB download area at www.abb.com/flow. Ordering information in the data sheet 15 Additional documents Note All documentation, declarations of conformity, and certificates are available in ABB's download area.
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E … 16 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 65
VA Master FAM540 METAL CONE VARIABLE AREA FLOWMETER | OI/FAM540-EN REV. E Notes...