Chapter 4 Register Configuration
(7) Channel status
F
Channel status
[9W]
(8) Receive byte length information
F
Receive bytes
[10W]
(9) Trailing code information
F
Trailing code
[12W]
Trailing code:Set to 0DH by default durling power on an cold start.
(10)Receive timeout information
F
Receive timeout
[13W]
Receive timeout : 0.1 to 60 sec. (setting : 1-600)
Receive timeout is set to 1 sec. (10) by default during power on and cold start.
16
Parameter 9W contain the control signal status.
E
D
C
B
No use
Parameter 10W contain the receive byte count.
E
D
C
B
Parameter 12W contain the trailing code of the transmission text.
This code can be rewritten with the MWRITE instruction to change the trailing
code.
E
D
C
B
A
No use
Parameter 13W contain the receive timeout interval between characters of the
receive data. Receive timeout error occurs if the interval between received data
characters exceeds this timeout interval.
E
D
C
B
Receive timeout is not checked if it is set to 0.
A
9
8
7
6
DSR
Bit
Nmae
1:DSR enable
7
DSR
0:DSR disable
A
9
8
7
6
Receive byte(0 to 320 bytes)
9
8
7
6
A
9
8
7
6
Receive timeout
5
4
3
2
No use
Description
5
4
3
2
5
4
3
2
Trailing code
5
4
3
2
model 2000 CIF Module(CF611)User's Manual
1
0
1
0
1
0
1
0