Parameter assignment / addressing
6.3 Configuring PROFIBUS DP
Application example
The system consists of a synchronous master (DP master) and at least one SIMOTION D4x5‑2
synchronous slave (DP slave). The synchronous master contains the master axis; the
synchronous slave contains the following axes:
● The axes in the SINAMICS Integrated of the D4x5‑2 synchronous slave must exhibit high
performance with a servo cycle clock of 1 ms and an internal DP cycle of 1 ms. This requires
that the internal fast PROFIBUS DP be decoupled from the slower external PROFIBUS DP.
● The PROFIBUS DP has, for example, a cycle time of 4 ms due to the quantity framework
on the bus; in all cases, its cycle time exceeds that of the cycle clock of the internal DP
interface.
● The master values are transmitted via the DP bus. Further nodes can also be connected
to the DP bus, e.g. DP drives, distributed I/Os, etc.
Figure 6-5
6.3.6
Internal PROFIBUS interface with DP Integrated < 0.5 ms
Requirement
The minimum settable cycle clock for the internal PROFIBUS interface (DP Integrated) is 0.5
ms.
138
Example of a cycle clock scaling for PROFIBUS DP
Commissioning and Hardware Installation Manual, 03/2018, A5E33441636B
SIMOTION D4x5-2