Error information clear

This section explains the factors causing the ERR LED to be turned ON and the error code initialization (clear) for C24.
Factors causing ERR LED to turn ON
When any of the following errors occurs, its error code is stored in the buffer memory corresponding to the interface (CH)
where the error occurred, and the ERR LED turns ON.
Error factor
Parameter setting error
Mode switching error
On-demand execution error
Data transmission error
Data reception error
Modern function error
MC protocol send error
Monitoring device error
Predefined protocol function
error
Factors causing ERR LED to flash
When any parameter error was detected, the ERR LED flashes, and the buffer memory address which is set out of the range
of the parameter setting value is stored in the error address storage area (Un\G20224 to 20231).
Turning OFF the ERR LED and initializing the error codes
Turn 'Error initialization request' (YE) ON to turn the ERR LED OFF and initialize the error code.
• The buffer memory, which is a factor in turning the LED ON, is initialized.
• The protocol execution logs are not initialized.
27 TROUBLESHOOTING
448
27.1 Checking Module Status
Error code storage buffer memory
Address
Name
CH1
CH2
Un\G515
Parameter setting error, mode switch error
status
Un\G598
Un\G614
On-demand execution results
Un\G599
Un\G615
Data transmission result
Un\G600
Un\G616
Data reception result
Un\G545
Modern function error code
Un\G602
Un\G618
MC protocol send error code
Un\G8709
Un\G8965
Programmable controller CPU monitoring
function execution result
Un\G16450
Un\G16466
Predefined protocol function error code
Applicable protocol
MC
Nonpr
Bidire
Prede
ocedu
ctiona
fined
ral
l