Huawei PDU8000 User Manual page 67

Modular integrated pdc v1.0
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Integrated PDC V1.0
User Manual
Main
Second-Level
Menu
Menu
Issue 07 (2019-04-15)
Third/Fourth-Level
Menu
Set Rated
Current (A)
Threshold
Sys Defect
Volt Set (V)
Voltage
harmonic
alarm (%)
Current
harmonic
alarm (%)
System
overvoltage
(%)
Syst.
overvoltage
ack. t. (s)
System
undervoltage
(%)
Syst.
undervoltage
ack. t. (s)
Overload (%)
Overload ack.
time (s)
Overfrequency
(Hz)
Overfrequency
ack. time (s)
Copyright © Huawei Technologies Co., Ltd.
7 MDU Commissioning Guide
Function
Specifies the rated voltage of
each branch. The value ranges
from 0 to 100.
The value ranges from 0 to 60.
Specifies the voltage harmonic
alarm threshold. The value ranges
from 1.0 to 30.0.
Specifies the current harmonic
alarm threshold. The value ranges
from 0.0 to 30.0.
Specifies the upper alarm
threshold relative to the rated
voltage. The value ranges from
105.0 to 125.0.
Specifies the duration for
acknowledging an overvoltage
alarm. The value ranges from 1 to
10.
Specifies the lower alarm
threshold relative to the rated
voltage. The value ranges from
75.0 to 95.0.
Specifies the duration for
acknowledging an undervoltage
alarm. The value ranges from 1 to
10.
Specifies the overload alarm
threshold relative to the rated
load. The value ranges from
100.0 to 120.0.
Specifies the duration for
acknowledging an overload
alarm. The value ranges from 1 to
10.
Specifies the overfrequency alarm
threshold relative to the rated
frequency. The value ranges from
1.0 to 10.0.
Specifies the duration for
acknowledging an overfrequency
alarm. The value ranges from 1 to
10.
Preset
Value
32
20
30.0
30.0
120.0
1
85.0
5
100.0
1
1.5
5
60