Line Connection Via A Ground-Fault Circuit Interrupter - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.8.5

Line connection via a ground-fault circuit interrupter

In addition to protective measures against direct and indirect contact, selectively tripping
AC/DC-sensitive residual-current circuit-breakers (Type B) can be used.
Danger
Residual-current circuit-breakers alone are not permissible to provide protection against
direct and indirect contact.
Note
A direct connection to a power system with selectively tripping AC/DC-sensitive residual-
current circuit-breakers is only possible with the 5 kW, 10 kW, 16 kW and 36 kW Line
Modules because suitable residual-current devices with higher ratings are not available as
qualified products.
Figure 2-20
Equipment Manual for Booksize Power Units
Equipment Manual, (GH2), 03/2006 Edition, 6SL3097-2AC00-0BP3
Residual-current circuit-breaker (RCCB)
Line Connection Booksize
2.8 Line connection variations
2-35