Connecting the Cables

Connecting to Supervised Contacts

Connect the contact cables to each of the 4 available inputs. Each
contact must be fitted with the appropriate balancing resistors
supplied with the kit. Place the resistors next to the contacts
themselves, as illustrated in Figure 3.
Figure 3. Connecting the Supervised Contact Cables
Yellow resistor: 1210 Ohm 1%
White resistor: 392 Ohm 1%
Close contact resistance: 296 Ohm
Open contact resistance: 1210 Ohm
INSTALLATION
contact 4
contact 3
white
white
yellow
yellow
J4
J5
J3
J1
J2
contact 2
contact 1
white
white
yellow
yellow
J4
J3
J2
J1
JP2
JP3
SW1
SW1
LED1
Page 5