Db Assignment; Instance Db For Fb 58 "Tcont_Cp - Siemens SIMATIC Manual

Pid temperature control
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Appendix
A.3

DB Assignment

A.3.1

Instance DB for FB 58 "TCONT_CP"

Parameters:
Addr Parameter
Decl.
0.0
PV_IN
INPUT
4.0
PV_PER
INPUT
6.0
DISV
INPUT
10.0
INT_HPOS
INPUT
10.1
INT_HNEG
INPUT
A-2
Data
Range of
Initial
Type
values
Value
REAL
Depen-
0.0
dent on
the
sensors
used
INT
0
REAL
0.0
BOOL
FALSE
BOOL
FALSE
Description
PROCESS VARIABLE IN
An initialization value can be set at
the "Process Variable In" input or an
external process variable in floating-
point format can be connected.
PROCESS VARIABLE PERIPHERY
The process variable in the peripheral
I/O format is connected to the
controller at the "Process Variable
Peripheral" input.
DISTURBANCE VARIABLE
For feedforward control, the
disturbance variable is connected to
the "Disturbance Variable" input.
INTEGRAL ACTION HOLD IN
POSITIVE DIRECTION
The output of the integral action can
be blocked in a positive direction. To
achieve this, the INT_HPOS input
must be set to TRUE. In a cascade
control, the INT_HPOS of the primary
controller is interconnected to
QLMN_HLM of the secondary
controller.
INTEGRAL ACTION HOLD IN
NEGATIVE DIRECTION
The output of the integral action can
be blocked in a negative direction. To
achieve this, the INT_HNEG input
must be set to TRUE. In a cascade
control, the INT_HNEG of the primary
controller is interconnected to
QLMN_LLM of the secondary
controller.
PID Temperature Control
A5E00125039-02