Chapter 4 Operation and Function
4
18
2
Set the PF312.
• Turn off MD4, 5, 6, and 7 of MODE2 setup switch.
(When there is an error, hold transmission data and set both transmit and receive)
• Set MODE1 setup switch to 6. (32 word transmission)
3
Install each module and connect cables.
• Install each module on the base unit.
• Connect PF311 and PF312 with transmission cable.
(Turn on both terminating resistors with connector or module.)
• Connect the PC and PF311 with connection cable.
4
Set PF311 with the configurator (SyCon).
• Insert master (PF311) (select HMS Profibus-DP Master.)
• Insert slave (PF312) (select HMS AnyBus-S.)
• Set the slave transmission word count.
(Select 32 word transmission (IN/OUT: 64 bytes (32 words).)
• Set transmission speed with bus parameter.
• Download settings to PF311.
5
Set each station with integrated controller engineering tool.
• Set PF311 from the master side station.
• Set PF312 from the slave side station.
• Create S3 controller program and download it.
Run each controller.
6
• When transmission starts, check the status of the PF311 and PF312 LEDs.
Transmission is normal if they are as follows:
PF311...RDY, RUN, TOKEN, ACC on, ERR off
PF312...ONL, ACC on, OFL, DIAG off
7
Check the transmission data with each controller.
• Check that expected data is transmitted on the master and slave side.
Figure 4-4 Startup procedure example
See section 2.5
See section 9.3
See chapter 5
See chapter 6
See section 2.5