5.2.6 Connecting the pipe system to the aspirating smoke
Building Technologies
Fire Safety
Figure 16: Arrangement of drilled holes away from fittings
See also
Label for aspirating holes [
End caps [
detector
NOTICE
Connection between pipe system and aspirating smoke detector
Damage to the pipe system and/or the aspirating smoke detector
Do not glue the pipe system to the aspirating smoke detector! If the pipe
system has to be separated from the aspirating smoke detector for
maintenance work or repairs, components may be damaged.
The pipe system is installed.
The last 500 mm of the pipe system on the aspirating smoke detector must be
straight, such that flow turbulences can be eliminated before entering the
aspirating smoke detector.
1. Press a short pipe securely into the air inlet on the aspirating smoke detector.
2. Connect the pipe system and the pressed-in pipe piece to the aspirating smoke
detector.
The pipe system is connected to the aspirating smoke detector.
You will find more information in document A6V10334410. See the chapter
'Applicable documents [
28]
7]'.
Mounting/Installation
Installing the pipe system
28]
A6V10334435_g_en_--
2017-09-12
5
53 | 56