4. Parameters - overview

The Inverter contains a number of settings
which can be changed to tailor it for use in a
wide range of applications. These settings are
known as parameters.
Parameters are typically referred to by code or
number (eg. s2.04 = Rated Motor Current) with
a description available in the manual.

5. Parameters to set before use

Set the following parameters to allow the EFC
3600 to control a motor with Run, Stop and
Speed Control from the keypad.
See section 6 to learn how to set a parameter value.
5.1 Parameters to check and values to set
Parameter Description
b0.02
Access to additional parameters
b1.05
Maximum Frequency
b1.06
Upper Frequency
b1.07
Minimum Frequency
b1.08
Lower frequency mode
b1.20
Acceleration ramp in seconds
b1.21
Deceleration ramp in seconds
S0.00
V/F curve mode
S2.00
Rated motor frequency in Hz
S2.01
Rated motor speed in rpm
S2.02
Rated motor power in kW
S2.03
Rated motor voltage
S2.04
Rated motor current in A
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright
Drive Supermarket and must not be reproduced or altered without prior written permission.
The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the user before the Inverter is
operated for the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the EFC 3600 Inverter.
If any of the parameters have been changed
previously, follow the procedure in section 13
to reset the Inverter to Factory Defaults.
How to set
Set at
2
to enable Extended Parameters (
Maximum frequency of the
Inverter
Maximum frequency of
speed reference (eg. keypad dial) Set to
Set to
05.00
for most applications (Default is 00.00).
Set to
1
to enable Minimum Frequency.
Default is . Increase or decrease if required.
5
Default is . Increase or decrease if required.
5
Default is . Set to 1 if the motor is driving a Fan or Pump.
0
Default is 50.00. Change to 60.00 for 60Hz motor only - otherwise set at 50.00
Set to match motor nameplate - eg. 1380
Set to match motor nameplate - eg. 0.8 (for 0.75kW)
Set to match motor nameplate - eg. 230
Set to match motor nameplate - eg. 3.34
Default is 0 for Basic Parameters)
. Set to
50.00
for most applications.
.
©
The Inverter
.
50.00
for most applications.
Page 5