Analog Input - GE 745 TRANSFORMER MANAGEMENT RELAY Instruction Manual

Hide thumbs Also See for 745 TRANSFORMER MANAGEMENT RELAY:
Table of Contents

Advertisement

5.6 S4 ELEMENTS
The 745 has the ability to monitor any external quantity, such as bus voltage, battery voltage, etc., via a gen-
eral purpose auxiliary current input called the analog input. Any one of the standard transducer output ranges
0-1 mA, 0-5 mA, 4-20 mA, or 0-20 mA can be connected to the analog input terminals. The analog input is con-
figured in S2 SYSTEM SETUP / ANALOG INPUT and the actual values displayed in A2 METERING / ANALOG INPUT.
This section contains the settings to configure the analog input monitoring elements. Included are two analog
input levels, each with a programmable pickup threshold and time delay.
S ANALOG INPUT
S [ENTER] for more
a) ANALOG LEVEL 1 (2)
S ANALOG LEVEL 1
S [ENTER] for more
ANALOG INPUT LEVEL 1
FUNCTION: Disabled
ANALOG INPUT LEVEL 1
TARGET: Self-reset
5
ANALOG INPUT LEVEL 1
PICKUP: 10 uA
ANALOG INPUT LEVEL 1
DELAY: 50 s
ANALOG INPUT LEVEL 1
BLOCK: Disabled
5-76
This message indicates the start of the ANALOG INPUT section. To continue
these setpoints press
EN TE R
This message indicates the start of the ANALOG LEVEL 1(2) sub-section. To
continue these setpoints press
Range: Disabled / Enabled
Range: Self-reset / Latched / None
Select None to inhibit the display of the target message when the element
operates. Thus an element whose "target type" is None will never disable the
LED self-test feature because can not generate a displayable target
message.
Range: 1 to 65000 (steps of 1)
Enter the analog input value (in the units programmed) above which the
analog input level 1 element will pickup and start the delay timer.
Range: 0 to 60000 (steps of 1)
Enter the time that the analog input value must remain above the pickup
level before the element operates.
Range: Disabled / Logc Inpt 1 (2-16) /Virt Inpt 1 (2-16) / Output Rly 1 (2-8) /
SelfTest Rly / Virt Outpt 1 (2-5)
745 Transformer Management Relay

5.6.17 ANALOG INPUT

or press
for the next section.
M E SSA G E
or press
E N TE R
M E SSA G E
GE Power Management
5 SETPOINTS
for the next section.