6
C-Bus stations
Control terminal
Control terminal
Main CPU
CI11
(max.16)
6.1
Station
6.2
Type of station
12
Fire & Security Products
Siemens Building Technologies Group
The C-Bus network contains max. 16 stations (user connected)
within the limits stated below (CC, CI, CT, CK) are any stations in any arrangement pos-
sible
max. 64 AREAS
CT11
(max.15)
C-Bus network
– max. 16 stations
– 4 different types of stations
– loop line max. 1400m with G51 ø 0.8mm
I-Bus
Line–
Control–
modules
modules
Detector
Function unit within C-Bus network
Several stations can be located in the same or in geographically dispersed cabinets
Differentiated by function and represented by a certain module
Certain modules can be used for different types of stations
Types of stations available:
CI11
Combination of main CPU and operating unit (AlgoPilot)
CC11
Main CPU
CT11
Control terminal (AlgoPilot)
CA11
Parallel control terminal
Gateway (e.g. conversion of C-Bus protocol Õ CERLOOP protocol)
CK11
DMS7000/LMS
(management
system)
CERLOOP
CK11
Gateway
(max.15)
C-Bus
I-Bus
Main CPU
Line–
modules
CC11
(max.15)
Control–
modules
Detector
e4595e 6