5. Internal Memory Configuration and Functions
5.3. Operation parameters setting area
Filter value (addresses 6 – 9)
1.
If the filtering constant value is set to '0', temperature-converted value of the
sampled temperature will be the output instead of the filtered value as the specific
channel will not be filtered.
2.
If filtering constant value is set to '1 – 159' or '64001' or more, an error will occur,
and the value will be internally reset to 0.
92
Resistance Temperature Detector 2MLF-RD4A User's Guide
Figure 42 – Filter value
Address
6
7
8
9
Honeywell
Description
Channel 0 Filter Value Setting
Channel 1 Filter Value Setting
Channel 2 Filter Value Setting
Channel 3 Filter Value Setting
R200