Cs1115/Fc330A Direct Configuration - Siemens DMS8000 Application & Planning

Hide thumbs Also See for DMS8000:
Table of Contents

Advertisement

3.2.3

CS1115/FC330A direct configuration

Building Technologies
CPS Fire Safety
Fig. 20
RS-232 direct configuration example
System architecture
This configuration allows for integration of CS1115 (or FC330A) fire panels.
Communication/connection
Via serial line RS-232.
Subsystems that can be connected in this way
Type
Name
Fire panel
CS1115
FC330A
Additional components required for the various management station types
Type
Additional
components
Foreign station
OPC client head end
OPC Server
Fire CNDL Driver
MM8000
Fire CNDL Driver
Limits and restrictions
Type
Version
MM8000
MP4.81
MK8000
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
Name
Any OPC DA/UA
compliant client
MK8000
NS8015
NS8015
Restrictions
Up to four serial connections to CNDL driver.
Automation level configurations
Supported by
MM8000
MK8000
MP4.81
MP4.81
X
X
X
X
Version
OPC DA2.0x
OPC UA 1.02
MP4.81
MP4.81
33
09.2016

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nk8000Mm8000Mk8000