Panasonic WH-MHF09G3E5 Service Manual page 52

Air-to-water heatpump system. mono bloc unit
Hide thumbs Also See for WH-MHF09G3E5:
Table of Contents

Advertisement

Setting 2: When heating priority is not set by control panel:
When Solar Priority is set/not set by control panel:
1. 3 ways valve control:
3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank
o
heat-up interval. Both modes will switch alternatively. Tank mode is the Initial running mode of this heat
+ tank mode (heating no priority).
2. Heat pump operation control:
During heating heat-up interval
o
 Follow normal heating operation
Under solar priority set condition:
Switch to tank heat-up interval and start counting tank heat-up timer when External Room Thermo
OFF AND solar 3WV OFF AND Tank temperature < THERMO ON TEMP (End Room Interval
Early) OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP AND solar 3WV OFF.
Under solar priority not set condition:
Switch to tank heat interval and start counting tank heat-up timer when External Room Thermo
OFF AND Tank < THERMO ON TEMP (End Room Interval) OR
Switch to tank heat-up interval and start counting tank heat-up timer when tank temperature <
THERMO ON TEMP.
* THERMO ON TEMP is defined Tank thermo ON/OFF condition below.
During tank heat-up interval
o
Heat pump tank target temperature = Tank set temperature or [60°C] whichever lower.
Heat pump Water Outlet set temperature is set to [63°C] during tank interval.
Initial Tank THERMO ON TEMP = heat pump tank target temperature + [-8°C].
Tank thermo ON/OFF characteristic:
THERMO OFF TEMP:
o
1. THERMO OFF TEMP = Heat pump tank target temperature + [0°C].
2. Tank temperature > THERMO OFF TEMP for continuous 10 seconds after heat pump off due
to water thermo, switch 3 ways valve to room side. End Tank heat-up interval and start count
heating heat-up interval.
3. Tank temperature > Tank set temperature + [2°C] for continuous 10 seconds, switch 3 way
valve to room side. End Tank heat up interval and start count heating up interval.
THERMO ON TEMP:
o
1. THERMO ON TEMP = Heat pump tank target temperature + [-8°C].
2. After heating heat-up interval, always detect tank temperature. Switch to next tank heat-up
interval when tank temperature < THERMO ON TEMP.
Characteristic of heat pump thermo ON/OFF under tank side condition
Water Outlet Thermo condition
Heat pump THERMO OFF TEMP:
o
1. Heat pump THERMO OFF TEMP = 63°C + [+4°C]
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, heat pump
OFF but water pump continue ON.
THERMO ON TEMP:
o
1. THERMO ON TEMP = Water inlet temperature, when heat pump thermo OFF + [-3°C].
Water Inlet Thermo condition
Heat pump THERMO OFF TEMP:
o
1. Water inlet temperature > [65°C] for continuous 60 seconds, heat pump OFF.
THERMO ON TEMP:
o
1. THERMO ON TEMP = Water inlet temperature < [65°C]
52