Parameterization As Defined By The Task - Siemens SICAM Q100 Device Manual

Power monitoring device and class a power quality recorder
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

8.7.3

Parameterization as Defined by the Task

Requirements
SICAM Q100 is electrically connected to the system and commissioned as described in chapter 6.7. Rated
voltages and currents at the measuring inputs are switched off.
Parameterization
NOTE
If you change settings in tabs, click Send on each tab to confirm the new setting. The settings are activated
only after the entire parameterization has been completed.
Start the user interface as described in chapter 8.2.1 (initial startup) or chapter 8.2.8 (start during
operation). Use the factory-preset IP address for this purpose.
On the Configure tab, configure the element AC measurement (see chapter 8.3.3.1.1) according to the
following topology specifications:
Figure 8-116
NOTE
If you are using Ethernet communication with IEC 61850 bus protocol (chapter 8.3.7.2) and change the
Network type, the device will restart.
SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A4, Edition 03.2018
Configure Tab, AC Measurement Example
8.7 Example of a Parameterization and Measured Value Evaluation
8 Operation at Use of a PC
269

Advertisement

Table of Contents
loading

This manual is also suitable for:

7kg95 series

Table of Contents