4.3. Logical Digital Input (LDI) Summary

Logical Digital Input (LDI) points are used for drive status monitoring such as terminal
ON/OFF conditions and fault status. The APG001Z supports 24 different logical digital
input points. All LDI points support COV (LDI points are capable of being characterized).
LDI points will respond to write point and memorize point commands, but will not change
their actual values or indicate override active.
Table 6 Logical Digital Input (LDI) Summary
Point
Number
21
23
25
27
28
33
36
37
38
39
70
71
72
73
74
75
76
77
78
79
80
81
86
93
Point
Name
FWD.REV
STOP.RUN
EXT1.2 ACT
DRIVE READY
AT SETPOINT
HANDAUTO ACT
FLN LOC ACT
CTL SRC
FLN REF1 SRC
FLN REF2 SRC
DI 1 ACTUAL (F)
DI 2 ACTUAL (R)
(DI 3 ACTUAL)
DI 4 ACTUAL(RES)
DI 5 ACTUAL(S1)
DI 6 ACTUAL(S2)
DO 1 ACTUAL (FL)
DO 2 ACTUAL (OUT1)
DO 3 ACTUAL(OUT2)
DO 4 ACTUAL(R2)
DO 5 ACTUAL(OUT5)
DO 6 ACTUAL(OUT6)
OK.ALARM
OK.FAULT
- 13 -
Factory
Slope
Intercept
Default
FWD
1
STOP
1
EXT1
1
NOTRDY
1
NO
1
AUTO
1
AUTO
1
NO
1
NO
1
NO
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OFF
1
OK
1
OK
1
E6581542①
ON (1)
OFF (0)
Text
Test
0
REV
FWD
0
RUN
STOP
0
EXT2
EXT1
0
READY
NOTRDY
0
YES
NO
0
HAND
AUTO
0
FLN
AUTO
0
YES
NO
0
YES
NO
0
YES
NO
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ON
OFF
0
ALARM
OK
0
FAULT
OK