Application class
Max. output fre-
quency
Torque control
Commissioning
5.4.4

Standard Drive Control

Procedure for application class [1]: Standard Drive Control
2.
3.
4.
5.
6.
7.
You have now configured the inverter.
Converter with CU230P-2 Control Units
Operating Instructions, 04/2015, FW V4.7 SP3, A5E34257946B AB
Standard Drive Control
550 Hz
Without torque control
Contrary to "Dynamic Drive Control", a
speed controller does not have to be set
When compared to "Configuration for ex-
perts"
Simplified commissioning using preas-
signed motor data
Fewer parameters
Select the I/O configuration to preassign the inverter interfaces.
The possible configurations are listed in Sections: Factory setting of the
interfaces (Page 86) and Default setting of the interfaces (Page 88).
Set the applicable motor standard and the inverter supply voltage.
Select your motor.
Enter the motor data according to the rating plate of your motor.
If you have selected a motor based on its article number, the data has
already been entered.
Set the most important parameters to suit your application.
Select the application:
• [0] Constant load: Typical applications include conveyor drives
• [1] Speed-dependent load: Typical applications include pumps and
fans
5.4 Commissioning with a PC
Dynamic Drive Control
240 Hz
Speed control with lower-level torque control
Fewer parameters when compared to "Configu-
ration for experts"
Commissioning
141