ABB RXPDK 21H Connection And Settings Manual

Directional time-overcurrent relay

Advertisement

Quick Links

ABB Network Partner AB
Version 2.1
1MRK 000 117-48
Fig. 1
Front layout
CONNECTION:
The RXPDK 21H relay requires a dc-dc converter type RXTUG for auxil-
iary voltage supply +24 V. Connection of voltage RL shall be made only
when the binary input is used.
The relay is delivered with a short-circuiting connector RTXK for mounting
on the rear of the terminal base. This connector will automatically short-cir-
cuit the current input when the relay is removed from its terminal base.
NOTE! The auxiliary voltage supply should be interrupted or the output cir-
cuits should be blocked to avoid the risk of unwanted alarm or tripping, be-
fore the relay is plugged into or withdrawn from its terminal base.
RXPDK 21H
Directional time-overcurrent relay
CONNECTION AND SETTING GUIDE
Rated current of the relay, I
LED indicators:
In serv. (green): indicates relay in service.
Start I
>(yellow): indicates operation of I
α
Trip I
> (red): indicates operation of I
α
I>> (red): indicates operation of I>> (no time delay).
I
> (Low set directional stage):
α
Potentiometer (P1) for setting of the operate value for the function I
Potentiometer (P2) for setting of the inverse-time factor k or definite-time delay t for the func-
tion I
>.
α
10-pole programming switch (S1) for setting of the scale-constant I s , time-delay
characteristic, definite-time delay and characteristic angle α.
Potentiometer (P3) for setting of the characteristic angle α for the function I
I>> (High set non-directional stage):
Potentiometer (P4) for setting of the operate value for the function I>>.
Reset push-button.
(available variants: 1 A or 5 A)
r
> (no time delay).
α
> after the set time delay.
α
110-220V
48-60V
RL
313
315
316
318
326
328
Fig. 2
1MRK 509 024-WEN
>.
α
>.
α
Bin1
Bin2
111
121
112
122
113
123
0V
Iα>
324
314
325
Iα>
317
331
341
I>>
327
117
114
115
116
+24V 0V -24V
Terminal diagram
Page 1
Replaces -
110-220V
48-60V
RL
0V
120
Ur
0V
Ir
Ir
0A

Advertisement

loading

Summary of Contents for ABB RXPDK 21H

  • Page 1 1MRK 000 117-48 Fig. 1 Front layout CONNECTION: Bin1 Bin2 The RXPDK 21H relay requires a dc-dc converter type RXTUG for auxil- 110-220V 110-220V iary voltage supply +24 V. Connection of voltage RL shall be made only 48-60V 48-60V when the binary input is used.
  • Page 2 When the ”Reset” pushbutton is depressed during normal operating conditions, all LEDs except "In serv." will light up. When connecting RXPDK 21H to the auxiliary voltage, the relay performs a self test. The ”In serv.” LED is alight, after per- forming the self test and when the relay is ready for operation.
  • Page 3 ABB Network Partner AB 1MRK 509 024-WEN Directional time-overcurrent relay Page 3 Version 2.1...