1MRS759117 A
REX640
Engineering Manual
Application configuration in the Application Configuration tool
•
Protection and control functions can be configured as needed.
•
The configuration made in Application Configuration is saved to make the
interfaces and signals available for other engineering tools within PCM600, for
example, for Parameter Setting.
Parameter setting and configuration in the Parameter Setting tool
•
The setting values are checked and adjusted with the Parameter Setting tool.
HMI engineering in Graphical Display Editor
•
It is possible to create new pages, configure pages by adding widgets, set page
visibility to different user categories, create single-line diagrams (shown on the
LHMI and the WHMI) and symbols, and to provide language translations for the
LHMI elements.
Communication protocol engineering
•
The communication engineering details are protocol-dependent.
•
The connectivity package creates the IEC 61850 configuration for vertical
communication automatically and it is often directly suitable for IEC 61850
client configuration. Either IEC 61850 Configuration tool or IET600 is needed
for configuring horizontal and vertical communication.
•
The Communication Management tool is used for other protocols; for example
Modbus.
The protection relay restarts automatically when writing a relay
configuration where changes have been made. It is not possible to
communicate with the protection relay during restart.
Relay engineering process
Section 2