3.6. "16 (0x10) Write Multiple Registers" function

This Modbus request is used to write a value continuously to contiguous inverter parameter.
Request format:
Byte
0
Function Code = 0x10
1
Communication No. of Starting Parameter Hi
2
Communication No. of Starting Parameter Lo
3
Number of Parameters Hi (0)
4
Number of Parameters Lo (1 - 123)
5
Byte Count (B = 2 × Number of Registers)
6
First Parameter Data Hi
7
First Parameter Data Lo
・・・
・・・・・・・・・・・・・・・・
B+4
Last Parameter Data Hi
B+5
Last Parameter Data Lo
Response format:
Byte
0
Function Code = 0x10
1
Communication No. of Starting Parameter Hi
2
Communication No. of Starting Parameter Lo
3
Number of Parameters Hi (0)
4
Number of Parameters Lo (1 - 123)
Exception response format:
Byte
0
Function Code = 0x90
Exception Code
01: Illegal Function
1
02: Illegal Data Address
03: Illegal Data Value
04: Slave Device Failure
When you use this Modbus request, the value is written to the EEPROM.
Meaning
Meaning
Meaning
Notes
29