Siemens SICAM AK Manual page 59

Rtus. redundancy,
Table of Contents

Advertisement

In the OPM system technique select the node Address of the redundant BSE's under
C4:CP-2017/PCCX25
Enter the following data (valid for BSE and AU redundancy)
Column name/
Parameter
Red_sync reg-Nr.
Red_sync comp-Nr.
Red_sync BSE-Nr.
In the OPM system technique select the node Synchronization parameter under C4:CP-
2017/PCCX25:
SICAM RTUs, SICAM AK Redundancy
DC2-026-2.07, Edition 10.2016
Description/Value
Region number of the other element of the
redundancy pair (BSE); for CPU redundancy
the value 254 is to be entered (own AU)
Component number of the other element of the
redundancy pair (BSE)
BSE number of the other element of the
redundancy pair
The mirroring of the
parameter is otherwise not
possible.
The mirroring of the
parameter is otherwise not
possible.
The mirroring of the
parameter is otherwise not
possible.
Unrestricted
Redundancy via SCA-RS
Comment