C80 Series Connection and Setup Manual
19 Appx.2: EMC Installation Guidelines
19.6 EMC Countermeasure Parts
19.6.1 Shield Clamp Fitting
The effect can be improved by directly connecting the cable's shield sheath to the grounding plate as shown below.
Install the grounding plate near the outlet (within 10cm) of each panel, and press against the grounding plate with the
clamp fitting.
If the cables are thin, several can be bundled and clamped together.
To provide sufficient frame ground, install the grounding plate directly on the cabinet or connect with a grounding wire.
Ground Plate #D
Ground Plate #E
Clamp fitting A
Clamp fitting B
Outline drawing
Earthing plate
2-
Installation hole
M4 screw
A
B
100
86
70
56
L1 (maximum dimension
when it is open)
Clamp fitting
(Fitting A, B)
View of clamp section
17.5
5
hole
6
22
35
C
Enclosed fittings
30
Clamp fitting A×2
-
Clamp fitting B×1
L2 (reference dimension)
25
12
Peel the cable sheath at the clamp section.
Cable
Earthing plate
Cable
Shield sheath
Clamp fitting
L2
(Note 1) Screw hole for wiring to earthing plate in cabinet.
(Note 2) The earthing plate thickness is 1.6mm.
253
(77)
(54)
L1
[Unit: mm]
IB-1501452-C