Threshold value
Dropout
Time multiplier
Number of value pairs for the operate characteristic
curve
X values of the operate curve
Y values of the operate curve
Number of value pairs for the dropout characteristic
curve
X values of the dropout characteristic curve
Y values of the dropout characteristic curve
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout
Minimum absolute dropout differential
Protection-class current transformer
Instrument current transformer
Reset of the Integration Timer
Instantaneous
Disk emulation
Direction Determination
Type
Forward range
Dropout differential forward/reverse range
Directional sensitivity
Times
Operate time with time delay = 0 ms
Extension of the operate time during operation with
transformer inrush-current detection
63
If you have selected the method of measurement = RMS value, do not set the threshold value under 0.1 l
64
OOT (Output Operating Time): additional delay of the output medium used, for example 5 ms with fast relays
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-A, Edition 05.2018
1 A @ 50 and 100 Irated
63
5 A @ 50 and 100 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
11.10 Directional Overcurrent Protection, Phases
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
Disk emulation
Instantaneous
0.05 to 15.00
2 to 30
1.00 p.u. to 66.67 p.u.
0.00 s to 999.00 s
2 to 30
0.05 p.u. to 0.95 p.u.
0.00 s to 999.00 s
95 % of 1.1 ⋅ threshold value
15 mA sec. (I
= 1 A) or
rated
75 mA sec. (I
= 5 A)
rated
0.5 mA sec. (I
= 1 A) or
rated
2.5 mA sec. (I
= 5 A)
rated
With dropout
Approx. < 0.90 ⋅ threshold value
With healthy voltages
With voltage memory 2 s
V
±88°
ref,rot
Unlimited for 1-phase and 2-phase short circuits
Dynamically unlimited, stationary for 3-phase short
circuits
Approx. 13 V phase-to-phase
Approx. 37 ms + OOT
64
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Approx. 10 ms
Technical Data
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
-
Increments of 0.01
Increments of 1
Increments of 0.01 p.u.
Increments of 0.01 s
Increments of 1
Increments of 0.01 p.u.
Increments of 0.01 s
.
rated,sec
1147