Motor Modules
4.3 Interface description
CAUTION
The temperature sensor must be connected in shielded form. The shielding must be
attached to the shield support of the motor module.
NOTICE
The KTY temperature sensor must be connected with the correct polarity.
NOTICE
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130 / PTC / PT100 probe in the stator windings.
Table 4- 6
Terminal strip X41, with order numbers 6SL3320–1Txxx–xAA0
Terminal
4
3
2
1
Max. connectable cross-section 1.5 mm
NOTICE
The KTY temperature sensor must be connected with the correct polarity.
NOTICE
The function of the EP terminals is only available when Safety Integrated Basic Functions
are enabled.
Note
The temperature sensor connection can be used for motors that are equipped with a KTY84-
1C130 / PTC probe in the stator windings.
154
Function
+ Temp
- Temp
EP +24 V (enable pulses)
EP M1 (enable pulses)
2
Technical data
Temperature sensor connection KTY84–1C130/PTC
Supply voltage: 24 VDC (20.4 V – 28.8 V)
Power consumption: 10 mA
Signal propagation delay times:
L → H 100 μs
H → L: 1000 μs
The pulse inhibit function is only available when Safety
Integrated Basic Functions are enabled.
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3