Technical Data - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

30
I/O card (RT) FCI2007-A1

Technical data

30.6
General
Supply
Maximum load on the outputs Total current from the supply output,
Supply output
Changeover contacts
RT alarm
Changeover contacts
RT fault
Monitored output
Fault
178
Building Technologies
Fire Safety
Technical data
Ground fault detection
Operating voltage
Quiescent operating current
Max. operating current (at max. load)
monitored and configurable outputs
Designation
Voltage
Current
Designation
Design
Switching voltage
Switching current
Designation
Design
Switching voltage
Switching current
Designation
Design
Output voltage
Output current
Loading capacity
Monitored for (active and inactive)
Measuring range, monitoring resistor
Range of load resistor (Rload)
Line resistance (both cables)
Monitoring tolerance
Measurement cycle
Status monitoring
Duration of monitoring interruption
after switchover
Duration of calibration
For FC2080 and FG2020 via communication
card
For FC2030 and FG2060 via PMI & mainboard
Vsys 20...30 V
70 mA with Vsys 24 V
5.6 A with Vsys 20 V
4.7 A with Vsys 24 V
Max. 4 A
'0 V', '27V2'
DC 26.4...27.6 V (DC 27.2 V -3 % +1.5 %)
Max. 2 A (electronically fused)
'AL_NO'; 'AL_COM'; 'AL_NC'
Relay output
Break or make contact
Activated in degraded mode
Max. DC 36 V
Max. 400 mA
'FAU_NO'; 'FAU_COM'; 'FAU_NC'
Relay output
Break or make contact
Activated in degraded mode
Max. DC 36 V
Max. 400 mA
'RT_Fault+'; 'RT_Fault-'
Load monitoring with calibration
Activated in degraded mode operation (fault
can be switched off)
DC 26.4...27.6 V (DC 27.2 V -3 % +1.5 %)
Max. 0.3 A
Max. 470 µF
Short-circuit
Open line
120...6000
150...4300
Max. 200
± 25 %
1 s
4 s
30 s
20 s
008837_q_en_--
14.05.2012