Toshiba TOSVERT VF-S15 Instruction Manual page 43

My function-s
Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

 Input function command 19: SET
 Input function command 20: RESET
The SET command turns on (sets) the output signal when the input signal is turned on, as
shown in the figure below, and holds the output signal ON even if the input signal is turned off.
The RESET command is used to turn off the output signal.
Input 1
Input 2
<Example> Output the input signal from Terminal F to the Terminal RY-RC as the hold signal by using SET
command. Reset the output signal by the signal from Terminal S1.
Prior setting
–
Step 1
Step 2
Unit 1
Step 3
Step 4
Step 1
Step 2
Unit 2
Step 3
Step 4
–
Setting
Output
Resetting
Fig. 8-5 Setting and resetting
Title
Parameter setting
a977  (Default)
f111 
f114 
f130 
a900 
a901 
a902 
a903  (Default)
a904  (Default)
a905  (Default)
a906 
a907 
a908 
a909  (Default)
a910  (Default)
a911  (Default)
a977 
Input 1
Input 2
Output
Set to "Disabled" of the My function-S.
Assign the "no function" to the Terminal F.
Assign the "no function" to the Terminal S1.
Assign the My function-S output 1 to the Terminal
RY-RC.
Read F input terminal signal. (LD F)
Send a signal to the My function-S output 1 by the
SET command, and output a hold signal from the
Terminal RY-RC.
NOP command (no operation)
NOP command (no operation)
Read S1 input terminal signal. (LD S1)
Cancel the hold command of the My function-S
output 1 by the RESET command.
NOP command (no operation)
NOP command (no operation)
Set to "My function-S always ON".
- 42 -
E6581865
Description

Advertisement

Table of Contents
loading

Table of Contents